Skip to content
Electrical

What Size Wire for a 50 Amp 240V Circuit?

The short answer is #6 copper, but a straight 50 A load, a long run, or aluminum all change it.

CrewCalcs EditorialUpdated Reviewed to NEC 2023How we keep this right
Short answer
For most 50 A, 240 V circuits, run #6 copper (or #4 aluminum) with a 50 A breaker and a #10 copper equipment grounding conductor. #8 copper is the NEC minimum for a purely non-continuous 50 A load on 75 °C terminals, but #6 covers continuous loads and gives voltage-drop margin, which is why it's the common choice.

Is the load continuous?

A load that runs for 3 hours or more (an EV charger, an electric water heater) is continuous, and conductors and the breaker must be sized to 125% of the load. A 50 A continuous load therefore needs conductors good for 62.5 A, which is #6 copper (65 A at 75 °C). A 50 A non-continuous load (an electric range, sized separately under its own demand rules) can use #8 copper at its 50 A ampacity.

The terminal rating caps you

Even with 90 °C wire like THHN/THWN-2, you almost always size to the 75 °C column, because breakers and lugs are rated 75 °C. So the 90 °C rating helps you with derating, but the number you compare against the load is the 75 °C ampacity: #8 Cu = 50 A, #6 Cu = 65 A.

Long runs: check voltage drop

Ampacity keeps the wire from overheating; voltage drop keeps the load working right. Over distance, a code-minimum conductor can drop too much:

  • #8 Cu, 50 A, 240 V at 150 ft drops about 4.9%, past the 3% guideline.
  • Bumping to #6 Cu brings that to roughly 3.1%; #4 Cu clears 3% comfortably.

The 3% / 5% figures are NEC informational notes, not hard requirements. But long feeders and EV chargers are exactly where they matter.

Aluminum runs one size up
Aluminum carries less per size, so a 50 A circuit wants #4 aluminum for continuous loads (or #6 Al at 50 A non-continuous). Use listed AL-rated lugs and an approved antioxidant, and torque to spec (NEC 110.14).
Run the numbers
Wire Size Calculator
Enter your load, distance, and install conditions. It runs the full NEC chain and shows every step.

Sources & references

Written by the CrewCalcs editorial team. We compute from published methods and validate every result against published code values. See our methodology and editorial standards. Guidance only; verify against the code edition your AHJ adopts.