HVAC · PT Chart

R-410A PT Chart

Pressure–temperature saturation chart for R-410A. Convert pressure to saturation temperature and back, or print the full table.

Convert
psig

Blend: use the dew value for suction (superheat) and the bubble value for liquid (subcooling).

R-410A saturation
40°F
Sat temp (dew)
40°F
Sat temp (bubble)
40°F

R-410A saturation table

psig at sea level · A1
Temp (°F)Bubble (psig)Dew (psig)
-401111
-3812.412.4
-3613.713.7
-341515
-3216.316.3
-3017.617.6
-2818.918.9
-2620.320.3
-2421.821.8
-2223.323.3
-202525
-1826.826.8
-1628.828.8
-1430.930.9
-1233.133.1
-1035.435.4
-837.837.8
-640.340.3
-442.842.8
-245.445.4
04848
250.650.6
453.453.4
656.156.1
85959
106262
126565
1468.168.1
1671.371.3
1874.674.6
207878
2281.581.5
2485.185.1
2688.988.9
2892.892.8
3096.896.8
32100.9100.9
34105105
36109.3109.3
38113.6113.6
40118118
42122.5122.5
44127.1127.1
46131.9131.9
48136.9136.9
50142142
52147.3147.3
54152.8152.8
56158.4158.4
58164.1164.1
60170170
62176176
64182182
66188.2188.2
68194.6194.6
70201201
72207.5207.5
74214.2214.2
76220.9220.9
78227.9227.9
80235235
82242.4242.4
84250250
86257.9257.9
88265.9265.9
90274274
92282.3282.3
94290.7290.7
96299.3299.3
98308308
100317317
102326.2326.2
104335.6335.6
106345.2345.2
108355355
110365365
112375.1375.1
114385.2385.2
116395.7395.7
118406.5406.5
120418418
122430.2430.2
124443.2443.2
126456.7456.7
128470.7470.7
130485485
132499.8499.8
134515.3515.3
136531.2531.2
138547.2547.2
140563563

Bubble vs. dew — how to read a blend

R-410A is a refrigerant blend, so it boils and condenses across a small temperature range (glide of ~0.2 °F (negligible)) rather than at a single point. The bubble line is where liquid starts to boil; the dew line is where the last vapor condenses. For charge checks: use the dew temperature for superheat on the suction line, and the bubble temperature for subcooling on the liquid line.

Frequently asked

What pressure should R-410A run at?
It depends on the saturation temperature you are targeting, not a single number. Read your gauge pressure, convert it to a saturation temperature with the chart above, then compare it to your line temperature for superheat or subcooling.
Does R-410A have temperature glide?
R-410A is a near-azeotrope with glide of ~0.2 °F (negligible). Use the dew (vapor) temperature for superheat on the suction line and the bubble (liquid) temperature for subcooling on the liquid line.
Is this R-410A PT chart accurate for charging?
Use it for field reference. Values come from published saturation data; still confirm against the equipment nameplate and manufacturer data for final charging.

Sources & references