HVAC · PT Chart

R-407C PT Chart

Pressure–temperature saturation chart for R-407C (provisional — verify before charging). Convert pressure to saturation temperature and back, or print the full table.

Convert
psig

Blend: use the dew value for suction (superheat) and the bubble value for liquid (subcooling).

R-407C saturation
55.2°F
Sat temp (dew)
55.2°F
Sat temp (bubble)
49.6°F

R-407C saturation table

psig at sea level · A1
Temp (°F)Bubble (psig)Dew (psig)
-4040
-385.11
-366.11.9
-347.12.8
-328.13.8
-309.14.7
-2810.25.6
-2611.36.6
-2412.47.7
-2213.78.8
-201510
-1816.511.3
-1618.112.7
-1419.814.2
-1221.615.9
-1023.517.5
-825.519.3
-627.521.1
-429.723
-231.825
03427
236.229.1
438.531.3
640.933.6
843.435.9
1045.938.4
1248.641
1451.343.6
1654.146.4
185749.1
206052
2263.155
2466.558
2669.961.2
2873.564.6
3077.268
3281.171.5
348575
3688.978.6
389382.3
409786
42101.189.8
44105.493.6
46109.897.6
48114.3101.7
50119106
52123.9110.5
54129115.1
56134.2119.9
58139.5124.9
60145130
62150.5135.3
64156.2140.7
66161.9146.3
68167.9152.1
70174158
72180.4164.1
74187170.3
76193.9176.7
78200.9183.3
80208190
82215.3196.9
84222.7203.9
86230.3211.1
88238218.4
90246226
92254.2233.8
94262.6241.8
96271.2250
98280258.4
100289267
102298.2275.8
104307.5284.8
106317.1294
108327303.4
110337313
112347.3322.8
114357.9332.7
116368.7342.9
118379.7353.4
120391364
122402.5374.9
124414.3386.1
126426.3397.5
128438.5409.1
130451421
132463.8433.2
134476.9445.7
136490.3458.5
138503.7471.3
140517484

Bubble vs. dew — how to read a blend

R-407C is a refrigerant blend, so it boils and condenses across a small temperature range (glide of ~7 °F (high glide)) rather than at a single point. The bubble line is where liquid starts to boil; the dew line is where the last vapor condenses. For charge checks: use the dew temperature for superheat on the suction line, and the bubble temperature for subcooling on the liquid line.

Frequently asked

What pressure should R-407C run at?
It depends on the saturation temperature you are targeting, not a single number. Read your gauge pressure, convert it to a saturation temperature with the chart above, then compare it to your line temperature for superheat or subcooling.
Does R-407C have temperature glide?
R-407C is a blend with glide of ~7 °F (high glide). Use the dew (vapor) temperature for superheat on the suction line and the bubble (liquid) temperature for subcooling on the liquid line.
Is this R-407C PT chart accurate for charging?
Use it for field reference. This chart is interpolated from published manufacturer anchor points and is marked provisional — confirm against the manufacturer PT chart before final charging.