HVAC · PT Chart

R-404A PT Chart

Pressure–temperature saturation chart for R-404A (provisional — verify before charging). Convert pressure to saturation temperature and back, or print the full table.

Convert
psig

Blend: use the dew value for suction (superheat) and the bubble value for liquid (subcooling).

R-404A saturation
58.3°F
Sat temp (dew)
58.3°F
Sat temp (bubble)
57.4°F

R-404A saturation table

psig at sea level · A1
Temp (°F)Bubble (psig)Dew (psig)
-4053
-386.14.1
-367.15.1
-348.26.2
-329.27.2
-3010.28.2
-2811.39.3
-2612.410.4
-2413.511.5
-2214.712.7
-201614
-1817.315.3
-1618.716.7
-1420.218.2
-1221.719.7
-1023.321.3
-82523
-626.624.6
-428.426.4
-230.228.2
03230
233.931.9
435.833.8
637.935.9
84038
1042.140.1
1244.442.4
1446.744.7
1649.147.1
1851.549.5
205452
2256.654.6
2459.357.3
2662.160.1
286563
306866
3271.169.1
3474.372.3
3677.575.5
3880.778.7
408482
4287.485.4
4490.888.8
4694.492.4
4898.196.1
50102100
52106.1104.1
54110.3108.4
56114.8112.9
58119.3117.4
60124122
62128.8126.6
64133.7131.3
66138.7136.1
68143.8141
70149146
72154.2151.1
74159.5156.4
76164.8161.8
78170.3167.3
80176173
82181.9178.9
84188185
86194.2191.2
88200.5197.5
90207204
92213.5210.5
94220.2217.2
96227224
98233.9230.9
100241238
102248.3245.3
104255.7252.7
106263.3260.3
108271.1268.1
110279276
112287.1284.1
114295.3292.4
116303.7300.8
118312.3309.3
120321318
122329.9326.7
124338.9335.5
126348.1344.4
128357.4353.6
130367363
132376.9372.8
134387382.9
136397.3393.3
138407.7403.7
140418414

Bubble vs. dew — how to read a blend

R-404A is a refrigerant blend, so it boils and condenses across a small temperature range (glide of ~0.7 °F) rather than at a single point. The bubble line is where liquid starts to boil; the dew line is where the last vapor condenses. For charge checks: use the dew temperature for superheat on the suction line, and the bubble temperature for subcooling on the liquid line.

Frequently asked

What pressure should R-404A run at?
It depends on the saturation temperature you are targeting, not a single number. Read your gauge pressure, convert it to a saturation temperature with the chart above, then compare it to your line temperature for superheat or subcooling.
Does R-404A have temperature glide?
R-404A is a near-azeotrope with glide of ~0.7 °F. Use the dew (vapor) temperature for superheat on the suction line and the bubble (liquid) temperature for subcooling on the liquid line.