HVAC · PT Chart

R-32 PT Chart

Pressure–temperature saturation chart for R-32. Convert pressure to saturation temperature and back, or print the full table.

Convert
psig

Single-component refrigerant: bubble and dew are the same.

R-32 saturation
36.4°F
Sat temp (dew)
36.4°F
Sat temp (bubble)
36.4°F

R-32 saturation table

psig at sea level · A2L
Temp (°F)Bubble (psig)Dew (psig)
-401212
-3813.613.6
-3615.115.1
-3416.616.6
-3218.118.1
-3019.619.6
-2821.121.1
-2622.722.7
-2424.424.4
-2226.126.1
-202828
-183030
-1632.232.2
-1434.534.5
-1236.936.9
-1039.439.4
-84242
-644.744.7
-447.447.4
-250.250.2
05353
255.855.8
458.858.8
661.861.8
864.964.9
106868
1271.371.3
1474.674.6
167878
1881.481.4
208585
2288.688.6
2492.492.4
2696.396.3
28100.2100.2
30104.3104.3
32108.5108.5
34112.7112.7
36117.1117.1
38121.5121.5
40126126
42130.7130.7
44135.5135.5
46140.5140.5
48145.7145.7
50151151
52156.5156.5
54162.2162.2
56168168
58173.9173.9
60180180
62186.1186.1
64192.4192.4
66198.8198.8
68205.3205.3
70212212
72218.9218.9
74225.9225.9
76233.1233.1
78240.5240.5
80248248
82255.7255.7
84263.5263.5
86271.5271.5
88279.6279.6
90288288
92296.6296.6
94305.4305.4
96314.4314.4
98323.6323.6
100333333
102342.6342.6
104352.4352.4
106362.5362.5
108372.7372.7
110383383
112393.4393.4
114404404
116414.8414.8
118425.8425.8
120437437
122448.5448.5
124460.3460.3
126472.3472.3
128484.5484.5
130497497
132509.8509.8
134522.9522.9
136536.3536.3
138549.7549.7
140563563

Bubble vs. dew — how to read this chart

R-32 is a single-component refrigerant, so it changes state at one temperature for a given pressure — the bubble and dew points are identical and there is no glide to account for.

Frequently asked

What pressure should R-32 run at?
It depends on the saturation temperature you are targeting, not a single number. Read your gauge pressure, convert it to a saturation temperature with the chart above, then compare it to your line temperature for superheat or subcooling.
Does R-32 have temperature glide?
No. R-32 is a single-component refrigerant, so the bubble and dew points are the same and there is no glide.
Is this R-32 PT chart accurate for charging?
Use it for field reference. Values come from published saturation data; still confirm against the equipment nameplate and manufacturer data for final charging.