Skip to content
HVAC · PT Chart

R-22 PT Chart

Pressure–temperature saturation chart for R-22. Convert pressure to saturation temperature and back, or print the full table.

Convert
psig

Single-component refrigerant: bubble and dew are the same.

R-22 saturation
68.3°F
Sat temp (dew)
68.3°F
Sat temp (bubble)
68.3°F

R-22 saturation table

psig at sea level · A1
Temp (°F)Bubble (psig)Dew (psig)
-400.50.5
-381.41.4
-362.42.4
-343.33.3
-324.24.2
-305.15.1
-2866
-2677
-2488
-2299
-2010.110.1
-1811.311.3
-1612.512.5
-1413.813.8
-1215.115.1
-1016.516.5
-817.917.9
-619.419.4
-420.920.9
-222.422.4
02424
225.625.6
427.327.3
629.129.1
830.930.9
1032.832.8
1234.734.7
1436.736.7
1638.838.8
1840.840.8
204343
2245.245.2
2447.547.5
2649.949.9
2852.452.4
3054.954.9
3257.557.5
3460.260.2
3662.962.9
3865.765.7
4068.568.5
4271.471.4
4474.474.4
4677.577.5
4880.780.7
508484
5287.387.3
5490.890.8
5694.394.3
5897.997.9
60101.6101.6
62105.4105.4
64109.2109.2
66113.2113.2
68117.3117.3
70121.4121.4
72125.6125.6
74130130
76134.4134.4
78139139
80143.6143.6
82148.3148.3
84153.2153.2
86158.2158.2
88163.2163.2
90168.4168.4
92173.7173.7
94179.1179.1
96184.6184.6
98190.2190.2
100195.9195.9
102201.8201.8
104207.7207.7
106213.8213.8
108220.1220.1
110226.4226.4
112232.8232.8
114239.4239.4
116246.1246.1
118252.9252.9
120259.9259.9
122267267
124274.2274.2
126281.6281.6
128289.1289.1
130296.8296.8
132304.6304.6
134312.7312.7
136320.9320.9
138329.1329.1
140337.2337.2

Bubble vs. dew — how to read this chart

R-22 is a single-component refrigerant, so it changes state at one temperature for a given pressure — the bubble and dew points are identical and there is no glide to account for.

Frequently asked

What pressure should R-22 run at?
It depends on the saturation temperature you are targeting, not a single number. Read your gauge pressure, convert it to a saturation temperature with the chart above, then compare it to your line temperature for superheat or subcooling.
Does R-22 have temperature glide?
No. R-22 is a single-component refrigerant, so the bubble and dew points are the same and there is no glide.
Is this R-22 PT chart accurate for charging?
Use it for field reference. Values come from published saturation data; still confirm against the equipment nameplate and manufacturer data for final charging.

Sources & references

Estimates for planning purposes only. Verify all results against the code edition adopted in your jurisdiction and with your Authority Having Jurisdiction (AHJ). This tool is not a substitute for a licensed HVAC contractor. See our methodology, sources, and code editions.